LV Drive

Addressing Voltage Output Limitations in the H100+ Drive

2025. 08. 21
Extra Form

Understanding the Issue

Drives often include output voltage limits to protect against transient voltage spikes, which can damage equipment or cause instability. These protective measures keep voltage within a safe range, preventing sudden fluctuations that may lead to failures.

Some applications need a drive to step down from 480V incoming to around 270V outgoing. While many drives support this, the H100+ has a minimum output voltage of 320V. This poses challenges for applications needing tighter voltage control for stability or protection.

 

Solution: Adjusting the Base Frequency

One way to work around this is by modifying the base frequency using:

Where:

  • Max Frequency is typically 60 Hz.
  • Output Voltage is 320V (minimum allowed).
  • Desired Output Voltage is the required value (e.g., 270V).

Since the drives are set at 60 Hz, software adjustments are needed to compensate. This shifts the voltage-to-frequency relationship to hit the desired voltage range.

 

Why Changing the Base Frequency Works

Drives follow the voltage-to-frequency (V/f) principle, maintaining a consistent ratio to ensure stable motor performance. Adjusting the base frequency shifts this ratio, allowing for lower voltage output without compromising torque or efficiency.

For instance, a default 60 Hz base paired with 320V can be scaled. Reducing the base frequency lowers the voltage output while keeping performance within safe, usable limits—no hardware changes required.